Voltage drop at recommended size
10.83 V · 4.51%
√3·K·I·L ÷ CM = 10.83 V on a 240 V circuit — 4.51% drop.
Formula: VD = 2·K·I·L/CM (1φ) · √3·K·I·L/CM (3φ) — NEC 210.19(A)(1) IN 4
Calculator 10 / NEC 210.19(A)(1) · 215.2(A)(1)
Size conductors so branch-circuit and feeder voltage drop stay within the 3% / 5% guidance, while never going below the NEC Table 310.16 ampacity floor.
The Table 310.16 column used for the ampacity floor. Per NEC 110.14(C), terminations rated ≤ 100 A are typically 60°C unless marked 75°C; larger equipment is typically 75°C. The 90°C column is not used for termination ratings.
Loading saved calculations…
Saved on this device · no cloud sync
Project / job name: —
Date: —
Site: voltforgelab.com
| System voltage | 240 V |
| Phase | Three-phase |
| Load current | 40 A |
| One-way length | 200 ft |
| Material | Copper (K = 12.9) |
| Target max drop | 5% |
| Terminal rating | 75°C |
Voltage drop at recommended size
10.83 V · 4.51%
√3·K·I·L ÷ CM = 10.83 V on a 240 V circuit — 4.51% drop.
Formula: VD = 2·K·I·L/CM (1φ) · √3·K·I·L/CM (3φ) — NEC 210.19(A)(1) IN 4
Recommended minimum size
8 AWG
Governed by: ampacity (the ampacity size is the larger one). 8 AWG is also the first size with ampacity ≥ 40 A in the 75°C column (50 A).
NEC Table 310.16 (ampacity) · NEC 210.19(A)(1) IN 4 (voltage drop guidance)
Engineering disclaimer: This design aid is not a substitute for engineering judgment. Confirm final design with a licensed professional engineer and the authority having jurisdiction.
Voltage drop at recommended size
10.83 V · 4.51%
√3 × K (12.9) × I (40 A) × L (200 ft) ÷ CM (16510) = 10.83 V, which is 4.51% of 240 V.
Formula: VD = 2·K·I·L/CM (1φ) · √3·K·I·L/CM (3φ) · NEC 210.19(A)(1) IN 4
Recommended minimum size
8 AWG
VD target 5% needs 8 AWG (4.51%), while the 75°C ampacity floor for 40 A needs 8 AWG (50 A). ampacity (the ampacity size is the larger one) governs → 8 AWG.
NEC Table 310.16 · NEC 210.19(A)(1) IN 4 · 215.2(A)(1)
| Size | Circular mils | VD (V) | VD (%) | Status |
|---|---|---|---|---|
| 14 AWG | 4110 | 43.49 | 18.12% | — exceeds target |
| 12 AWG | 6530 | 27.37 | 11.41% | — exceeds target |
| 10 AWG | 10380 | 17.22 | 7.18% | — exceeds target |
| 8 AWG | 16510 | 10.83 | 4.51% | ✓ recommended |
| 6 AWG | 26240 | 6.81 | 2.84% | ✓ VD OK |
| 4 AWG | 41740 | 4.28 | 1.78% | ✓ VD OK |
| 3 AWG | 52620 | 3.40 | 1.42% | ✓ VD OK |
| 2 AWG | 66360 | 2.69 | 1.12% | ✓ VD OK |
| 1 AWG | 83690 | 2.14 | 0.89% | ✓ VD OK |
| 1/0 AWG | 105600 | 1.69 | 0.71% | ✓ VD OK |
| 2/0 AWG | 133100 | 1.34 | 0.56% | ✓ VD OK |
| 3/0 AWG | 167800 | 1.07 | 0.44% | ✓ VD OK |
| 4/0 AWG | 211600 | 0.84 | 0.35% | ✓ VD OK |
| 250 kcmil | 250000 | 0.71 | 0.30% | ✓ VD OK |
| 300 kcmil | 300000 | 0.60 | 0.25% | ✓ VD OK |
| 350 kcmil | 350000 | 0.51 | 0.21% | ✓ VD OK |
| 400 kcmil | 400000 | 0.45 | 0.19% | ✓ VD OK |
| 500 kcmil | 500000 | 0.36 | 0.15% | ✓ VD OK |
| 600 kcmil | 600000 | 0.30 | 0.12% | ✓ VD OK |
| 700 kcmil | 700000 | 0.26 | 0.11% | ✓ VD OK |
| 750 kcmil | 750000 | 0.24 | 0.10% | ✓ VD OK |
| 800 kcmil | 800000 | 0.22 | 0.09% | ✓ VD OK |
| 900 kcmil | 900000 | 0.20 | 0.08% | ✓ VD OK |
| 1000 kcmil | 1000000 | 0.18 | 0.07% | ✓ VD OK |
Circular-mil areas per NEC Chapter 9 Table 8. The recommended size is the smallest size meeting BOTH the VD target and the 75°C ampacity floor.