Full-load current
14 A
Motor FLC from the applicable NEC table.
NEC Table 430.250
Calculator 01 / NEC 430
Enter motor nameplate basics for a traceable starting point on branch-circuit sizing.
Loading saved calculations…
Saved on this device · no cloud sync
Full-load current
14 A
Motor FLC from the applicable NEC table.
NEC Table 430.250
Branch-circuit conductor
14 AWG
Required ampacity: 17.5 A → 20 A copper (75°C).
NEC 430.22(A) · Table 310.16
Short-circuit protection
35 A breaker
Computed: 35 A (250% × FLC) → next standard size.
NEC 430.52(C)(1) · 240.6(A)
Motor controller / starter
NEMA Size 1
Minimum HP-rated controller; Size 1 supports 10 HP at 460 V. NEMA ratings use the 200 V column for 208 V systems (conservative convention).
NEC 430.83 · UL 508A
Overload relay setting
17.5 A
125% × FLC; set relay at or below this calculated maximum.
NEC 430.32(A)(1)