Calculator 15 / UL 508A §32

Control transformer

Size control power from sealed and inrush VA, with a conservative transformer selection and fuse guidance.

Control-circuit devices

Typical: 3–10×

Typical: 3–8×

Typical: 1–2×

Typical multipliers are guidance only; device nameplate and manufacturer transformer inrush capability govern.

Loading saved calculations…

Saved on this device · no cloud sync

Sealed load / minimum

110 VA / 137.5 VA

Sealed VA total and 125% design margin.

UL 508A §32.2.4

Inrush check

PASS

210 VA inrush vs approximately 750 VA momentary screening capacity.

Manufacturer guidance · UL 508A §32

Fuse guidance

Primary 167% · secondary 125%

Apply allowances to actual transformer FLA and select listed standard fuses.

NEC 430.72(C)

How this was calculated

  1. Sum sealed VA: 110 VA.
  2. Apply 1.25 design margin: 110 × 1.25 = 137.5 VA; round up to 150 VA standard size.
  3. Sum inrush VA (210 VA) and screen against approximately 5× selected rating; manufacturer data governs.
  4. Fuse primary at up to 167% and secondary at up to 125% of actual FLA, subject to NEC 430.72(C) conditions.
Engineering disclaimer: Verify transformer nameplate FLA, inrush, fuse class, control-circuit class, and UL 508A construction requirements.