Panel SCCR
5 kA at 480 V
Minimum of the main (100 kA) and all 1 branch effective ratings.
UL 508A SB4.2 (Method 1) · NEC 409.110
Calculator 09 / UL 508A Supp. SB
Evaluate the panel SCCR component-by-component per UL 508A Supplement SB Method 1 and compare it with the available fault current at the panel terminals.
Available fault current
IEEE 551-style transformer estimate — NOT an NEC table. Utility data wins; feeder impedance reduces fault current, so this transformer-terminal value is conservative.
Main OCPD
Prefilled from typicals (capped by class interrupting rating 200 kA); replace with the nameplate value. UL 248-8 · 0–600 A · 600 V.
Branch components
Branch 1
Often 100 kA with Class CC/J/RK1 fuses (marked combination).
Up to 10 rows. Per UL 508A SB4.2.1, an unmarked component is assumed 5 kA. Typical values are prefill guidance only — the nameplate ALWAYS governs.
Project / job name: —
Date: —
Site: voltforgelab.com
| System voltage | 480 V |
| Available fault current | 31.4 kA (estimate) |
| Main OCPD | Class J, 400 A, 100 kA SCCR |
| Branches | Branch 1: 5 kA, starter |
Panel SCCR
5 kA at 480 V
Minimum of the main (100 kA) and all 1 branch effective ratings.
UL 508A SB4.2 (Method 1) · NEC 409.110
Available fault current
31.4 kA
Transformer-terminal estimate; feeder impedance reduces fault current.
IEEE 551 transformer method — not an NEC table
Engineering disclaimer: This design aid is not a substitute for engineering judgment. Confirm final design with a licensed professional engineer and the authority having jurisdiction.
Panel SCCR
5 kA at 480 V
Minimum of the main (100 kA) and all 1 branch effective rating (per-branch: 1→5 kA).
UL 508A SB4.2 (Method 1) · NEC 409.110
Available fault current
31.4 kA
Transformer-terminal estimate: 1500 kVA, 480 V, 5.75%Z. Feeder impedance reduces fault current, so this value is conservative.
IEEE 551 transformer method — not an NEC table
Loading saved calculations…
Saved on this device · no cloud sync