Calculator 13 / NEC 310.15

Ampacity derating

Apply ambient-temperature and current-carrying-conductor adjustments to the NEC Table 310.16 base ampacity.

Conductor and installation inputs

Ambient factors use Table 310.15(B)(1) rows; CCC adjustment uses Table 310.15(C)(1). Terminal ratings under 110.14(C) can govern the usable base column.

Loading saved calculations…

Saved on this device · no cloud sync

Base ampacity

30 A

Base value at 30°C ambient and up to three CCC.

NEC Table 310.16 · 90°C copper

Correction factors

1 × 1

Ambient 30°C factor 1; 3 CCC factor 1.

NEC 310.15(B)(1) · 310.15(C)(1)

How this was calculated

  1. Look up 12 AWG copper in the 90°C Table 310.16 column: 30 A.
  2. Apply Table 310.15(B)(1) ambient factor 1 and Table 310.15(C)(1) CCC factor 1.
  3. 30 × 1 × 1 = 30 A.
Engineering disclaimer: Verify terminal temperature limitations under NEC 110.14(C), conductor insulation listing, raceway conditions, and AHJ requirements.