Capacitor kvar required
42.1 kVAR
100 kW × (tan 0.750 − tan 0.329).
IEEE Std 141 · NEMA MG 1
Calculator 17 / IEEE Std 141
Find the capacitor kvar needed to bring a load from its present power factor to a target power factor, with the before/after current impact.
kVAR = kW × (tan(cos⁻¹ PF₁) − tan(cos⁻¹ PF₂)). Capacitor ratings shown are typical catalog sizes — confirm availability with the vendor. Capacitor installation per NEC Article 460.
Loading saved calculations…
Saved on this device · no cloud sync
Project / job name: —
Date: —
Site: voltforgelab.com
| Inputs | 100 kW, PF 0.8 → 0.95, three-phase 480 V |
Capacitor kvar required
42.1 kVAR
100 kW × (tan 0.750 − tan 0.329).
IEEE Std 141 · NEMA MG 1
Recommended standard rating
50 kVAR
Nearest standard size at or above 42.1 kVAR.
Typical catalog ratings
Apparent power before / after
125 / 105.26 kVA
Corrected load draws -19.74 kVA less.
kVA = kW ÷ PF
Line current before / after
150.35 / 126.61 A
At 480 V, three-phase.
I = kVA × 1000 ÷ (V × √3)