Calculator 17 / IEEE Std 141

Power factor correction

Find the capacitor kvar needed to bring a load from its present power factor to a target power factor, with the before/after current impact.

Load and correction inputs

kVAR = kW × (tan(cos⁻¹ PF₁) − tan(cos⁻¹ PF₂)). Capacitor ratings shown are typical catalog sizes — confirm availability with the vendor. Capacitor installation per NEC Article 460.

Loading saved calculations…

Saved on this device · no cloud sync

How this was calculated

  1. Reactive-power demand: tan(cos⁻¹ 0.80) = 0.750; tan(cos⁻¹ 0.95) = 0.329.
  2. kVAR = 100 kW × (0.7500.329) = 42.1 kVAR.
  3. Round up to the nearest typical catalog rating (50 kVAR) and verify the vendor's offered sizes.
  4. Apparent power falls from 125 to 105.26 kVA, reducing line current from 150.35 to 126.61 A at 480 V.
Engineering disclaimer: Capacitor placement, switching, and harmonics require an engineering study; follow NEC Article 460 (enclosures, discharge resistors, disconnecting means) and verify capacitor ratings with the manufacturer. Confirm final design with a licensed professional engineer.